13 Start-up
The spring pre-tension is factory set to 360° and is normally not necessary to adjust. If adjustment has to be carried out, see "Reducing/Increasing the Spring pre-tension (SPTE)" on page 76.
Check and adjust the microswitch (1), controlling the lock kick, by turning the black plastic cam (2) when power is off.
This lock kick is optional and only used with fire doors to give a lock kick at power failure.
13.1 Adjusting the door stop
- Close the door.
- Turn the potentiometer
SPTEto 0° (if not already on 0°). - Switch on the electrical power (the operator will find its closed position) and make sure the LED is on.
- Open the door to required open position, plus approx. 15 mm, by turning the potentiometer
SPTEon the CU-200, clockwise. - When stop arm is on top of the operator, lift the door stop arm up and mount it on the splines, as close as possible to the stop block1). Fine-adjust if necessary with the screw on the stop arm2).
- When stop arm is on the bottom of the operator, loosen the stop ring and the stop arm. Mount the stop arm on the splines, as close as possible to the stop block3). Mount the stop ring. Fine-adjust if necessary with the screw on the stop arm4).
- Close the door by turning the potentiometer
SPTEto 0° and let the door close.
SPTE is more than 0°.
(Reference to diagram components: 1. Door stop arm, 2. Stop block, 3. Fine-adjustment screw)
13.2 Auto-learn – automatically sets back and latch check (recommended)
This learning is performed by pushing the LEARN BUTTON (LRN).
- Switch on the electrical power (the operator will find its closed position) and make sure the LED is on.
- Before the learning procedure starts, make sure that the door has been properly closed i.e., not by force.
- A new learn must be carried out in following situations:
- If any of the parameters SPRING PRE-TENSION and CLOSING TORQUE (CLTQ) are changed after performing a learn.
- If any of the arm system DIP-switches are changed.
- A confirmation by pushing the learn button is enough in following situations:
- If any changing of the MAT-dip.
- When replacing any of the extension units.
- When changing of Lock 12/24V.
- Learn can be carried out with activation units and locks connected.
- The back-check will be automatically adjusted to 10° and 1 second before open position. The latch-check will be automatically adjusted to 10° and 1.5 seconds before closed position.
13.2.1 Push the LEARN BUTTON (LRN)
When the learn button is pressed the status LED starts to blink and will not stop until learn is concluded.
The learn cycle starts with sensor detection, during which the door will stand still. When the door starts moving the spring tension and door inertia are measured and the door open and close position is saved. When the learn is concluded the back-check, latch-check, opening time and closing time are calculated. The changed settings affect the behavior of the installation and must be verified.
13.2.2 Double doors
For double doors, the primary door must be learned first and thereafter the secondary door. When the secondary door is learned, the primary door will open up to fully open position during the learning phase of the secondary door.
The doors can also be learned separately before connecting the sync cable. In case of rebated doors and separate learning, the primary door must be held open before the secondary door learn is carried out.
13.3 General adjustment
- Set the hold open time with the potentiometer on the control unit.
- Adjust the opening speed (
OPSP). Turning clockwise increases the speed. - Adjust the closing speed (
CLSP). Turning counter-clockwise decreases the speed. - Connect the required activation units.
- Check that the installation complies with AHJ (Authority Having Jurisdiction).
See the "Guide for installers of Powered Pedestrian Swing Doors", document PRA-0006, for calculation of speed.
13.4 Connection of activation units and accessories
See sensor manuals for mounting and adjustments. Protective device shall comply with EN 12978.
Door mounted
When sensors are used in order to avoid contact with the door leaf it is required that the presence detect sensor and the presence impulse sensor fulfills Performance Level = d according to EN ISO 13849-1. These sensors shall also be monitored (tested) by ASSA ABLOY SW200 door operator.
Wiring / Pin Configuration
| Color | Terminal | Function |
|---|---|---|
| Brown | A | Inner impulse (1) |
| Yellow | B | Outer impulse (2) |
| Pink | C | Key Impulse (3) |
| Violet | D | Presence impulse (4) |
| White | E | Presence detection (5) |
| Blue | F | Off (6) |
| Red | G | Kill impulse NO (7) |
| Green | H | Kill impulse NC, fire alarm, smoke detector (8) |
| Black | I | Fire alarm reset (9) |
| Grey | J | Standard* |
DIP A7 to ON (for primary sensor)
DIP B4 to ON for presence impulse
DIP B4 to OFF for presence detection