7. Commissioning
(also after reset to factory settings (Fact-Setup))
7.1 Requirements
- The operator is fully installed and correctly connected to the door leaf.
- The parts supplied separately such as program switch and activator (radar detector, night/bank key switch) are mounted and connected.
- The motor is cold.
7.2 Commission the operator
-
Switch on the operator on the power switch.
The display shows a sequence of characters that reflect the current processing state. The system is being checked.
- 2 back and forth segments in the middle indicate that the control unit is waiting for internal signals (maximum 1 second).
- 2 drop-down underscores show that the installation position can be entered. If entered incorrectly, the characters in the display are upside down.
-
Press the lower key (only necessary for the first commissioning).
The device detection "runs" through the display. ED 100 or ED 250 and the firmware version (represented by XX XX).
Small, rotating "o" and "P" show that further parameterization is required (only during the first commissioning or after reset with factory settings).
- The parameters: Set the mounting type (AS), frame reveal depth (rd) and door width (Tb), see “9 Parameterization”.
7.3 Change parameters
- Press for 3 seconds to open the parameters menu.
- Press to select the desired parameter.
- Press to display the parameter value.
- Press to select the value to change.
⇒ the value flashes. - Press to set the desired value.
- Press to save the changed value.
- Press to return to the parameters menu.
- Press to select the next parameter.
After leaving the parameterization mode, the display shows a small, rotating "o" and "P".
7.4 Carrying out a learning cycle
The learning cycle must be carried out with a cold motor. During the learning cycle, the door leaf must not be moved or stopped manually, otherwise the control unit cannot correctly determine the parameters. Safety sensors and activators are switched off during the learning cycle so that the learning cycle process is not disturbed. Smoke detectors and operator function shutdown are active.
- Secure the range of motion of the door leaves.
-
Close the door and switch the program switch to the OFF position.
A rotating "o" and "O" show that a learning cycle is required.
-
Press the key for 3 seconds.
The door performs different movements and the display shows a sequence of characters. The movements of the door leaf must not be stopped.
The door is in 70° position and is waiting for the opening width to be set.
- Move the door to the desired open position and press the button.
If the spring tension is too low, the display shows the small rotating "o" and "F".
- In this case, the spring tension must be increased and the learning cycle restarted.
Door is ready for operation
7.5 Commissioning of a 2-leaf unit
- Put the active door leaf into operation.
- After the learning cycle, switch the program switch to PERMANENTLY OPEN.
- Put the passive door leaf into operation.
Additional parameterization
-
On active door leaf:
- Set parameter >dL< (door type) to "1".
- Set parameters >Ad< (end run angle) to the desired value.
-
On passive door leaf:
- Set parameter >dL< to "2".
7.6 Zero point detection after mains reset
During the zero point detection, the display shows the small rotating "o" and "b".
7.7 Commissioning with integrated smoke detector
See ED Cover Basic RM, ED Cover VARIO RM mounting instructions.
8. Install upgrade cards
8.1 Requirements:
- The operator must be fully assembled.
- The learning cycle has been successfully completed.
- The power supply is switched on.
- The program switch is in the “Off” position.
- The information display indicates a state of rest.
8.2 Use in 2-leaf units
- Full Energy:
- The Full Energy Upgrade Card can be installed on one or both operators.
- Fire protection:
- The Fire Protection Upgrade Card must be installed on both operators.
- Professional:
- The Professional Upgrade Card is only installed on the operator for the active door leaf. For the EVAC or SPV functions in 2-leaf systems, 1 Professional Upgrade Card is required for each operator on which the functions are to be used.
- DCW:
- The DCW Upgrade Card is only installed on the operator to which DCW products are connected.
8.3 Installing the first Upgrade Card
-
Insert the Upgrade Card into the slot, see “3.1 Operator system”.
- During insertion, the yellow LED flashes once.
- The data is transferred. The communication between the modules is indicated by slow flashing of the green LED.
- The corresponding function is now released and can be activated, see “9 Parameterization”, parameters F1-F8.
- The unit is ready for operation.
8.4 Installing further upgrade cards
Additional Upgrade Cards can be installed. The first installed Upgrade Card takes over the function of the container module. All installed functions can be used as long as the container module is installed in the operator system.
- Remove the container module.
-
Insert the next upgrade card.
The function is copied into the operator system and the upgrade card is devalued.
- Remove the upgrade card as soon as the yellow LED lights up.
-
Plug in the container module.
The control unit detects the container module and saves the new function in it.
Slow flashing of the green LED indicates the successful operation, the function can be activated, see “9 Parameterization”, parameters F1-F8.
The following must be taken into account during installation:
- If the container module is removed, the previously released functions are deactivated after some time.
- To reinstall the upgrade cards, an extended factory setting must be carried out.
- When replacing the control unit, the container module is connected from the old control unit to the new control unit. The new control unit synchronizes with the container module, and all functions are available again.
- If a upgrade card is already activated, this is rejected. This is indicated by quick flashing of the yellow LED. A devaluation of the module is then not carried out.
- When plugging in the container module to a third-party, the container module is rejected. This is indicated by quick flashing of the yellow and green LEDs. The module can only be firmly synchronized with one control unit.
8.4.1 Installing the Fire Protection Upgrade Card
- Install the Fire Protection Upgrade Card as described in points 8.3 and 8.4.
- Insert the supplied light conductor into the larger drill hole in the side cover on the power switch side.
8.4.2 Accessible WC Upgrade Card
- Install the Accessible WC Upgrade Card as described in points 8.3 and 8.4.
- Turn the ED 100, ED 250 off and then on again so that the functions are taken over.