9. Parameterization
After carrying out the learning cycle, the operator can be operated with the basic parameters. The system also offers the option to adapt the travel parameters to the actual conditions as well as to activate advanced functions. These parameters should be set according to the user's wishes during commissioning.
Mounting Type
Defines the installation configuration.
- 0: Frame reveal mounting hinge side, slide rail pulling EN 4-6
- 1: Frame reveal mounting opposite side to the hinge, scissor arm pushing
- 2: Frame reveal mounting opposite side to the hinge, slide rail pushing
- 3: OHC_R (Overhead Concealed Right)
- 4: OHC_L (Overhead Concealed Left)
- 5: Frame reveal mounting opposite side to the hinge, scissor arm pushing EN7
- 6: Frame reveal mounting hinge side pulling with CPD lever
- 7: Frame reveal mounting hinge side pulling with CPD 250 lever
Frame Reveal Depth
The frame reveal depth is set in 10 mm increments. The required dimensions can be found in the assembly drawings.
Door Leaf Width
The rebate is included in the door leaf width. The door width is specified in 100 mm increments.
Door Type
- 0: Single-leaf door
- 1: 2-leaf door, active door leaf, overlapping door leaf
- 2: 2-leaf door, passive door leaf, overlapping door leaf
- 3: 2-leaf door, active door leaf, edgeless door leaf
- 4: 2-leaf door, passive door leaf, edgeless door leaf
Opening Speed
The opening speed refers to automatic operation. Country-specific limits must be adhered to and checked after setting. The full setting range is only available with an installed Full Energy Upgrade Card. The admissibility of the setting is checked by internal monitoring.
Closing Speed
The closing speed refers to automatic operation. Country-specific limits must be adhered to and checked after setting. The full setting range is only available with an installed Full Energy Upgrade Card.
Hold-open Time
The time the door remains open for people to pass through. Starts after contact/voltage is opened at inputs (activator, safety, Push & Go) and door is open. In Low Energy mode, min. 5s is recommended. Increments: 1s (0-30s), 5s (>30s).
Night/Bank Hold-open Time
Specific hold-open time for key switch/night bank inputs.
Hold-open Time (Manual Open)
Applies after purely manual opening, including Power Assist activation or stop by sensor strip.
BS Wall Blanking
Input signal from hinge side safety sensor is ignored beyond this angle. Required when door opens against a wall/obstacle. Minimize this area for personal protection. A quick-flashing point on display indicates blanking is active when exceeded.
Safety Sensor Test
Configures testing for safety sensors (e.g., IRS-2, EN 16005, DIN 18650). Level (high/low active) must match the sensor.
- 0: Test Off (for IRS-2)
- 1: BS test sensor - level high active
- 2: BGS test sensor - level high active
- 3: BS & BGS test sensor - level high active
- 4: BS test sensor - level low active
- 5: BGS test sensor - level low active
- 6: BS & BGS test sensor - level low active
Pulse from Safety Sensor (Opposite Hinge)
- 0: Signal ignored when door is closed.
- 1: Safety sensor can trigger opening impulse when closed.
Suppression of BS Safety Sensor (Initial Travel)
- 0: BS safety sensor not active during initial travel (hidden).
- 1: BS safety sensor active during initial travel.
Unlocking Time
Delay before door opens after pulse. Setting "0" means no "pressing" before unlocking.
Unlocking Force
Strength of push in CLOSED direction before opening. Relieves limit electric strike releases. Higher values increase arm load; keep as low as necessary.
PR Module Test
Tests Power Reserve module (for SVP-2000 DCW / M-SVP 2000 DCW). Automatically activated if fire protection module is detected. Test runs every 24h.
- 0: Test off
- 1: Test active
Static Force (Opening Direction)
Basic parameter for wind load control. Check actual forces on door leaf after learning cycle to meet local standards.
Static Force (Closing Direction)
Basic parameter for wind load control. Check actual forces on door leaf after learning cycle to meet local standards.
End Stop Pulse
Motorized end stop action to overcome seals/locks. Increase cautiously to avoid damage.
End Stop Angle
Angle from which motorized end stop pulse is effective.
Locking Force
Force applied permanently after end stop to hold door CLOSED against wind. 0=Off, 1-9=On.
Push & Go
If ON (1), door opens automatically if manually moved 4 degrees from CLOSED. Requires "hd" (door closer mode) to be 0.
Program Switch Type
- 0: Internal program switch active.
- 1: External program switch (contacts). Internal plug removed.
- 2: External DCW program switch. Internal plug removed.
- 3: Via TMS software.
- 4: Via Door Pilot interface, TMS, or DCW.
EPS DCW Behavior (After Mains Reset)
- 0: Returns to last known position.
- 1: Switches to OFF position (insurance-related lock requirement).
Internal Program Switch Power Up Delay
- 0: Immediate function takeover.
- 1: 10s delay. Useful if passing through detector after changing door settings.
Daily Activation
- 0: Door locked at CLOSED position.
- 1: Door not locked in automatic mode at CLOSED. Locking contact remains switched permanently (requires 100% duty cycle opener).
Status Relay Function
- 0: Deactivated.
- 1: Switches at CLOSED position.
- 2: Switches at OPEN position.
- 3: Faults reported.
- 4: Door CLOSED and locked.
- 5: Fault or information reported.
- 6: Switches when open further than status contact angle.
Control Unit Output 1G (with Input 4/4a)
- 0: Independent of contact 4/4a.
- 1: Switches as soon as 4/4a opens. Impulses 100% duty-opening time required. Not for DCW motor locks.
Cycle Counter
Displayed in steps of 10,000. Display 4 = 40,000. 99 = 990,000+.
Delete Error Memories
Set to 1 to delete memory. Automatically resets to 0.
Reset Service Interval (Yellow LED)
Set to 1 to reset cycle/time counter to 200,000 cycles / 12 months.
Factory Settings Level
Triggered by pressing Fact Setup key > 8s.
- 1: Standard. All parameters default. Upgrade cards retained.
- 2: Extended. All parameters default. Upgrade cards deleted from memory.
Door Closer / Automatic Mode
- 0: Automatic mode. Optimized for motion detectors/safe closing. Reverses on blockage.
- 1: Door closer mode. Mainly manual opening. Stops on blockage. Optimized for manual open. Power Assist only available here.
Power Assist Settings
Start Angle
Angle where function takes effect. Smaller = more sensitive.
Support Force
Strength of support. Higher = easier to open. 0=Deactivated. Only in door closer mode.
Support Manual Mode (CLOSED)
Support force in CLOSED position.
Upgrade Cards
Available Cards:
- Fire Protection: Required for fixed systems (EN 14637). Enables detector input. Activates Full Energy automatically.
- Full-Energy: Unlocks full adjustment range for speed/force.
-
Professional:
- Power Surge: Door control without hold-open time (toggle open/close).
- Extended Hold-open: 0-180s.
- Nurse/Beds: Separate/joint opening of 2-leaf doors.
- EVAC / SPV: Emergency/Smoke control modes. Input 43 control.
- Disabled WC: Accessibility functions.
- DCW: Enables DCW bus components (program switches, motor locks, etc).
Additional Configuration
- Configuration of COM1 Interface
- 0 = Handheld | 1 = Door Pilot App / TMS
- Backcheck (Manual Opening)
- Range: 5–40 degrees. Default: 10. Braking start angle counting back from opening angle.
- Door Thickness
- 0–99 mm. Default: 35. Influences measured opening angle.
- Operator Switch-off Direction
- 0 = Opener contact | 1 = Closer contact.
- Night/Bank Operating Direction
- 0 = Closer contact (Key switch) | 1 = Opener contact (RWA/GLT).
- Trigger Hold-open by Reversing
- 0 = Off (Manual button req) | 1 = On (Manual pull 10 degrees triggers).
- Trailing Angles (2-leaf)
- 0–30 degrees. Delay for passive leaf.
- Hinge Gap
- +/- Adjustment for door angle calculation.