6. Connecting Accessories
Installation Requirements:
- Clamp the connection cables to the connectors and plugs on the connection board.
- Maximum Total Load: 1.5 A at terminals 1, 1G, and 3.
- Terminal 1G Load: Maximum 1 A.
- Cable Length: Maximum of 30 m when using J-Y(ST)Y 0.8 mm.
6.1 Assignment of Terminals (Standard)
Overview of the general terminal assignments for standard operation modes.
Power & DCW Interface
| Terminal / Function | Specifications |
|---|---|
| DCW Upgrade Card | Interface for DCW accessories. |
| Fire Protection Upgrade Card |
If installed, either an RM-ED or terminating resistor 18K must be connected.
Note: Terminal 18K is included with the Upgrade Card. |
| Power Output (Terminals 1, 1G, 3) |
24 V DC/AC + 15% output for external accessories. Max Load: 1.5A total (Max 1A on terminal 1G). |
Input & Output Signals
Locking Relay
- Max. 1 A / 48 V DC/AC
- Terminals: NO, NC, COM
- Includes Locking Feedback (0V, Input)
Program Switch Inputs
- Off
- Automatic
- Permanent Open
- Partial Open / Exit Only
- Night/Bank
Safety Sensors
- Hinge Side: 24V, 0V, Test Output, Signal Input (Terminals 1, 3, etc.)
- Opposite Hinge Side: 24V, 0V, Test Output, Signal Input
Activators
- Inside Activator: 24V (Terminal 1), Signal (Terminal 4)
- Outside Activator: 24V (Terminal 1), Signal (Terminal 3)
Status Relay
- Configurable output status signals.
Important Note on EVAC/SPV:
When using EVAC/SPV, input 43 changes to input EVAC/SPV. EVAC opening pulse with activated EVAC function is only possible via input 35.
Smoke Detector: Functions based on shutdown operator function.
6.2 Terminal Assignment: Accessible WC Upgrade Card
Configuration for Barrier-Free WC (Toilet) applications.
Required Components
The door unit must be equipped with the following components for this mode:
- Quiescent current door opener or a suitable motorized panic lock.
- Inside: Door handle, Surface text button, Status display "Engaged".
- Outside: Knob, Surface text button, Status display "Free/Engaged".
Specific Terminal Functions (WC Mode)
| Status / Input | Terminal Function / Layout |
|---|---|
| Status Relay Output | Indicates "Free" or "Engaged" via NO/NC/COM contacts (Max 1A/48V). |
| Emergency Switch | Can be optionally mounted inside and outside. Included in the scope of some upgrade cards. |
| Forced Flushing | Controls for forced flushing: 1s impulse, 24 V DC (via Output). |
Recommendation: dormakaba recommends that the accessible WC also be integrated into an emergency call system provided by the customer.