Record STA 16 Fault Signals & Status Codes

Status and Fault Signals - Record STA 16 Manual

In the event of an irregularity, the system automatically switches from the operating mode level to the status level. Change is made approx. every 5 seconds between status and operating mode level. No status display is given in the remaining levels.

Characteristic of the status level are 2 or more rapidly flashing LEDs (of 6 total). This permits a maximum of 58 different status numbers to be output. A status with "W" is a warning, which is not followed by switching of the fault output relay.

LED Status Codes (BDE-E)

Overview of LED patterns and Status Codes
LEDs Active Status Details
1 2 3 4 5 6 Code & Description
03 AKI sensor active > 60s
04W Manual operation
05 AKA sensor active > 60s
06 Unlocking error
09 Battery fuse blown
10 Locking error; door not closed
12 Battery defective (voltage too low)
14 Locking n/o contact defective
20* Door leaf interception error
26 Overload at FEM outputs
29 TOS is not locked in "locking" mode
30 TOS is locked in "automatic" mode
31 EMERGENCY STOP button operated
33 Error ELS 1
34 Error ELS 2
37 Wrong motor current
38 Excess temperature motor 1
39 Overload on +24 V supply
40 Excess temperature motor 2
41 Motor 1 - thermal sensor defective
42 Motor 2 - thermal sensor defective
43 Incremental generator defective
44W Motor current time product high
45 Motor current time product too high
46 Control unit defective
47 Ext. safety active > 60 s
48 NSK or SÖK active
49* Alarm CO48 Ventouse
50 Control unit CPU2 is faulty
54W Calibration run
55 Power failure
58 FEM connection interrupted
59 ELS sensor active > 60 s
60 Parameter memory defective (EEPROM)
61 SSK - sensor active > 60 s
62 BDE has no priority

* These status numbers only exist in CO48 systems

Detail Description of Status Indications

Note: A status can usually be deleted by pressing the key for 5s (reset). This produces a new start in the control unit.

03 AKI sensor active longer than 60 s

Automatic resetting, provided in order, or by service fitter

04W Manual control / Manual operation

System is in manual mode.

05 AKA sensor active longer than 60 s

Automatic resetting, provided in order, or by service fitter

06 Unlocking fault

Possibly lock jammed.

Reset by service fitter

09 Battery fuse blown

Jumper J13 possibly missing if no battery present. Fuse possibly defective or cable interrupted.

Reset by service fitter

10 Locking fault

Possibly obstruction in door.

Automatic resetting provided door is closed and locking possible

12 Battery defective (voltage too low)

Battery exchanged by service fitter. Automatic resetting.

14 Locking n/o contact defective

VAK contact possibly wrongly adjusted or interrupted.

Reset by service fitter

20 Door leaf interception error

Buffers (end stops) are possibly adjusted the wrong way. Possible wire break at the magnet.

Reset by pressing the program key "record" for 5 sec.

26 Overload at FEM outputs

Reset by service fitter. Remove overload and generate reset with STG key.

29 TOS is not locked in the "locking" mode

Automatic reset if ok or service fitter

30 TOS is locked in the "automatic" mode

Automatic reset if ok or service fitter

31 EMERGENCY STOP operated

Reset by resetting EMERGENCY STOP key

33 Fault ELS 1 during ELS learning cycle

Door possibly too wide or ELS sensor dirty. ELS cable or ELS head possibly defective.

Reset by cleaning or service fitter

34 Fault ELS 2

See status 33

37 Defective motor current

STG or ATE defective.

Reset by service fitter

38 Excess temperature motor 1

Manual control effective. Door leaves possibly too heavy or there is too much friction.

Reset by motor cooling or by service fitter

39 Overload on +24 V supply

Possibly too many external units connected.

Reset by service fitter

40 Excess temperature motor 2

See status 38

41 Motor 1 - thermal sensor defective

Motor possibly not connected. Sensor in motor possibly defective or cable broken in sensor lead.

Reset by service fitter

42 Motor 2 - thermal sensor defective

See status 41

43 Incremental generator defective

Generator cable possibly not connected or cable broken in lead. Motor possibly blocked.

Reset by service fitter

44W Motor current time product high

Possibly too much traffic or door leaves too heavy. Minimum hold-open time extended to approx. 4 s.

Automatic resetting by cooling

45 Motor current time product too high

Possibly too much traffic with door leaves too heavy. Hold-open time extended to approx. 20 s.

Automatic resetting by cooling

46 Control unit defective

Includes the following individual faults: EPROM, RAM, Watchdog, Imax, ImaxT, difference on SHE-EXT.

Reset by service fitter

47 External safety sensor active longer than 60 s

Automatic resetting, if in order, or by service fitter

48 Emergency fail close contact or emergency opening contact active

Interrupted.

Automatic resetting if contact recloses

49 Alarm CO48 Ventouse

Interruption sandow switch or interruption at the switch. Close Ventouse, tighten sandow or adjust switch.

Reset is carried out automatically

50 Control unit CPU2 is faulty

Reset by service fitter

54W Calibration run

Wait until door is closed.

Automatic resetting after completion of 3 openings

55 Power failure

Battery operation if battery present.

Automatic resetting when power restored

58 FEM connection interrupted

The connection did exist but is now interrupted. Check the cable, FEM may also be faulty.

59 ELS sensor active longer than 60 s

Automatic resetting, if in order, or by service fitter

60 Parameter memory defective (EEPROM)

Change control unit.

Reset by service fitter

61 SSK sensor active longer than 60 s

Automatic resetting, if in order, or by service fitter

62 BDE has no priority

Because higher-level signal present (e.g. time switch).

Automatic resetting by releasing BDE key