Assa Abloy SW300 Electrical Connections & Setup Guide

Assa Abloy SW300 - Electrical Connection Manual
  • Place the electric switch easily accessible from the operator.
  • The operator is intended for fixed installation only with cable entry from the back plate. It is not designed for cable entry from the side plates.
  • If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.

See Auto-learn – automatically sets back and latch check (recommended) on page 68.

Mains Connection

  1. Switch off the mains power.
  2. Connect the plug contact to the wall socket or connect to the mains switch.

Alt. 1 (Standard)

Remove the protective lid (1) and connect the incoming mains power through the strain relief (2) to the connection block (3).

Alternative Connections (Optional)

  • Alt. 2 (Optional)
  • Alt. 3 (Optional)
  • Alt. 4 (Optional)

12.1 Control Units

12.1.1 CU-300

Overview of the Control Unit connections and DIP-switches.

DIP-Switch Settings & Potentiometers

Function Label Description
HOT / KHOT Hold open time / Key hold open time
OPSP Opening speed
CLSP Closing speed
CLTQ Closing torque
POAS Power assist
LED External LED indicator (OK=Green, ALARM=Red)

Connection Terminals

  • 1 PAG: Push & Go
  • 2 MAT: Safety mat
  • 3 SOS: Stop on stall
  • 4 AD: Activation delay
  • 5 INV: Inverse installation
  • 6 AS1: Arm system setting 1
  • 7 AS2: Arm system setting 2

12.1.2 Arm System Selection

Note! Connect the motor cable to either PUSH or PULL depending on arm system. After changing any system selection a new LEARN must be carried out.

Factory set arm configuration is PUSH. If other is required, select arm configuration on the DIP-switches according to the table below (ON=1, OFF=0):

Type of Arm System AS 2 (DIP 7) AS 1 (DIP 6) Description
PUSH 0 0 Standard Push Arm
PULL 0 1 Standard Pull Arm
PULL-220 (Narrow Door) 1 0 Reveal 0 - 65 mm
Sliding PUSH 1 1 Sliding Arm Application

12.1.3 Extension Units EXU-SI / EXU-SA

Overview of expansion modules. Installed using Torx T10 and 5mm nut driver.

  • Includes Tag strip (long 2pcs EXU, short 1pc EXU).

12.1.4 Extension Unit EXU-SI

This extension unit has inputs for electro-mechanical lock, program selector, KILL function, OPEN/CLOSE, KEY opening and outer impulse.

Terminal Functions

Terminal Label Function Description
1 +24 V DC Power supply
2 OPEN Program selector
3 EXIT Program selector
4 OFF Program selector
5 UNL Unlocked signal from lock
6 KRST KILL reset (Manual/Auto via jumper)
7 KILL KILL impulse
8 KEY Key impulse (1.5 - 30s)
9 O/C OPEN/CLOSE impulse (latching relay)
10 OIMP Outer impulse
11 GND Ground
12 Electro-mechanical locking device (-)
13 + Electro-mechanical locking device (+) 12V/24V

Note! Lock only functions when Program Selector is in OFF or EXIT.

Lock Kick: Position OFF: Smooth closing (no lock). Position ON: Powerful closing (with lock).

12.1.5 Extension Unit EXU-SA

This extension unit has inputs for door mounted sensors (presence impulse on approach, presence detection on swing path). Includes relay output for error indication, KILL output, Lock output or door indication.

Terminal Functions

Terminal Label Function Description
1 NO Relay output: External error / KILL OUT / Lock indication OR Open/closed door indication (24V, 1A)
2 COM
3 NC
4 24 V DC Power (+)
5 QTST Monitoring of presence detection/impulse
6 PDET Presence detection (NC)
7 PIMP Presence impulse (NC)
8 GND Ground

12.1.6 How to cut the jumper on the sync cable for double doors

Note! The connection/marking of the sync cable determines which of the operators is the MASTER and SLAVE.
  • Astragal door: Master must open before Slave. Slave must close before Master.
Cut the jumper with color Door design / Function
SLAVE side MASTER side Jamming Astragal Closing Opening
No cutting No cutting No No Synchronous Synchronous
No cutting Cut black No Yes Asynchronous Synchronous
Cut red No cutting Yes Yes Asynchronous Asynchronous
Cut red Cut black Double egress

12.1.7 & 12.1.8 Double Door Installations & Settings

Settings configuration for MASTER and SLAVE units.

Function SLAVE MASTER
Common
Program selection X
Opening time X
Closing time X
Hold open time X
Close / Continue to open when obstructed X
PAG On/Off (X)* X
Level of Power assist (X)* X
Extended closing force X
OPD Impulse or Mat Logic Impulse X
Selection of operating mode on battery X
Individual
Lock / Unlock signal voltage X X
Locked without / with power X X
Lock release Enable / Disable X X
Open Delay Time X X
Lock kick Enable / Disable X X

* For "Double egress doors", these functions must be set separately for MASTER and SLAVE.

Note! Locks on MASTER and SLAVE doors must be connected to corresponding control units. Inner/Outer impulses can be connected to either or both.

12.2 Sensor Cable Inlet

Diagram reference for cable routing. See Article No. 1007567.

12.3 Reset and Indication Device for Fire Doors

Connections for Article No. 1009828 (Reset & Indication device) and Smoke Detectors.

  • Terminal A/B: Connection points for reset device and smoke detectors.
  • CL: Optional connection leg (840/Optional).