News

ASSA ABLOY SW100: Advanced Settings & Configuration Guide

ASSA ABLOY SW100 Advanced Settings | Technical Manual

14. Advanced Settings

This section covers advanced configuration for the SW100 operator, including learning procedures, resetting to defaults, and configuring parameter groups.

14.1 Learn with Advanced Setting of "Back- and Latch-Check"

Prerequisite: See the prerequisites for performing a "learn" under the heading Auto-learn – automatically sets back and latch check (recommended) on page 51.

  1. Push the button once or twice as for auto-setting.
  2. Stop the door at the required back-check position.
  3. The door reverts towards the closed position.
  4. Remove the stop.
  5. Stop the door at the required latch-check position.
  6. The door reverts to learn the fully open position.
  7. Remove the stop.
  8. The door reverts to the closed position.

14.2 Revert to Default Values for "Back- and Latch-Check" (Level 1)

  1. Disconnect batteries if any.
  2. Disconnect the mains.
  3. Press the LEARN BUTTON (LRN) and keep it depressed.
  4. Connect the mains.
  5. Watch the ERROR LED.
  6. Release the LEARN BUTTON after 1 flash (LED is out).
  7. The BACK CHECK, LATCH CHECK, and OPEN POSITION have now reverted to default values.
  8. Disconnect the mains.
  9. Next time the mains is connected, a new learn is needed to be run, and the operator will use the default values.

14.3 Changing Group of Parameters (Level 2)

  1. Disconnect batteries if any.
  2. Disconnect the mains.
  3. Press the LEARN BUTTON (LRN) and keep it depressed.
  4. Connect the mains.
  5. Watch the ERROR LED. Wait for the sequence (3s, 3s, 1s).
  6. Release the LEARN BUTTON after 2 flashes (LED is out).

The ERROR LED flashes a number of short flashes that corresponds to the parameter group number. After a short pause, the LED will repeat the group number, and so on.

  1. Pushing the LEARN BUTTON once increases the parameter group number. When the highest parameter group number is reached, it will start with number 1 (default) again.
  2. Push the button until you get the requested parameter group. Ensure that the requested group of parameters has been selected by counting the number of flashes.
  3. Disconnect the mains.
  4. Next time the mains is connected, the operator will use the new group of parameters.

Note: When changing group of parameters, normally only the primary control must be configured in a double door application. When changing from or to group seven, both primary and secondary must be configured.

Parameter Groups Table

Parameter/Group 1 (Default) 2 3 4 5 6 7 8 9 10
Priorities See detailed parameter specificiation in official documentation for full group mappings.
Hold Open Time 1.5s 1.5s 1.5s 1.5s 1.5s 1.5s 1.5s 1.5s Infinite 1.5s
Battery Mode Convenience Power Save Power Save Power Save Power Save Power Save Power Save Convenience Power Save Power Save

*Refer to original documentation for complete matrix of Locked During Kill, Obstruction Mode, and Presence Detection settings per group.

14.4 Classification (Level 3)

  1. Disconnect batteries if any.
  2. Disconnect the mains.
  3. Press the LEARN BUTTON (LRN) and keep it depressed.
  4. Connect the mains.
  5. Watch the ERROR LED.
  6. Release the LEARN BUTTON after 3 flashes (LED is out).

Changing the Classification

The ERROR LED flashes an amount of short flashes that correspond to the classification number.

  • Push the button until you get the requested classification.
  • Disconnect the mains.

Next time the mains is connected, the operator will use the new classification.

The learn procedure must be carried out after a change of the classification setting.

Classification Table

Classification Mode Standard Opening Speed Closing Speed
1 Full power (Default) - Automatic limitation Automatic limitation
2 Low energy EN 16005 1.69 J / 3-6 s 1.69 J / 3-6 s

If classification 2 (Low energy) is used, the operator will automatically follow the speed limitation in EN 16005.

Speed Settings for Low Energy Mode

The table shows minimum opening time to back check or to 80° open or minimum closing time from 90° to 10° open.

Width of door leaf (mm) 50 kg 60 kg 70 kg 80 kg 90 kg
750 3.0 s 3.2 s 3.2 s 3.3 s 3.5 s
850 3.1 s 3.1 s 3.2 s 3.4 s 3.6 s
1000 3.2 s 3.4 s 3.7 s 4.0 s 4.2 s
1200 3.8 s 4.2 s 4.5 s 4.8 s 5.1 s

14.5 Overhead Presence Detection (OPD) Monitoring (Level 4)

  1. Disconnect batteries if any.
  2. Disconnect the mains.
  3. Press the LEARN BUTTON (LRN) and keep it depressed.
  4. Connect the mains.
  5. Watch the ERROR LED.
  6. Release the LEARN BUTTON after 4 flashes (LED is out).

Changing Status

  • Push the button until you get the requested monitoring status:
    • 1 = OFF (Default)
    • 2 = ON
  • Disconnect the mains.

Recommended Settings for Sensor SP34-M

Component Settings
Sensor DIP Switch Dip 1 = ON
Dip 2-8 = OFF
Interface DIP Switch Dip 1, 4, 7 = OFF
Dip 2, 3, 5, 6, 8 = ON

14.6 Lock Kick (Level 5)

  1. Disconnect batteries if any.
  2. Disconnect the mains.
  3. Press the LEARN BUTTON (LRN) and keep it depressed.
  4. Connect the mains.
  5. Watch the ERROR LED.
  6. Release the LEARN BUTTON after 5 flashes (LED is out).

Changing Status

  • Push the button until you get the requested lock kick status:
    • 1 = Basic (Default)
    • 2 = Enhanced
  • Disconnect the mains.

14.7 Lock Unlocked Status (Level 6)

Note! Only valid for locked without power = Fail secure.

  1. Disconnect batteries if any.
  2. Disconnect the mains.
  3. Press the LEARN BUTTON (LRN) and keep it depressed.
  4. Connect the mains.
  5. Watch the ERROR LED.
  6. Release the LEARN BUTTON after 6 flashes (LED is out).

Changing Status

  • Push the button until you get the requested status:
    • 1 = Lock is unlocked when door is not closed.
    • 2 = Lock is unlocked when door is 0-10 degrees from closed position, during opening.
  • Disconnect the mains.
Previous
Assa Abloy SW100: Cover Fitting & Safety Signage Guide
Next
Assa Abloy SW100: Spring Tension & Safety Adjustment Guide

Leave a Comment

Your email address will not be published.