System 20 Automatic Door Drive: User & Maintenance Manual

System 20 Automatic Door Drive - Operation & Maintenance Manual

Application Range

Notice

System 20 includes the following door drives for which these instructions apply: STA / TSA 20 or 21 or 22, Thermcord, Safecord

Target Groups (User)

This operating manual is intended for the target groups listed below:

  • Operating entity of the system: the person who is responsible for the technical maintenance of this system.
  • Operator of the system: the person who operates the system every day and has been suitably instructed.

The handling of the system is explained with the help of this operating manual. It forms the basis of fault-free working and gives instructions for the procedures to follow for rectifying any faults that may occur. Extracts of this document can also be made accessible to persons entrusted with the day-to-day operation of the system.

The operating entity of the system must read this operating manual before commissioning the system, and follow the safety instructions.

It is recommended that this document should be kept handy in the vicinity of the automatic system.

Door Care

The entire system, including the sensors and safety devices, can be cleaned with a moist cloth and standard commercial cleaners (non-scouring, do not use any solvents). First test the cleaners on a hidden (not easily visible) place. Keep all guides free of dirt.

Notice

It is recommended that for carrying out this work, the operating mode (Locked) or (Continuously open) be used, so as to avoid possible injuries from unwanted door movements.

Maintenance and Regular Inspection

Prior to carrying out the first commissioning and if required as well as in accordance with the applicable regulations - however at least twice a year – a technical inspection by a skilled service technician or an authorized partner must take place. We recommend performing maintenance at the same time.

Any due maintenance is indicated on the display of the BDE-D control unit. The interval for the edition of this message is determined by the number of opening cycles and/or the expiry of a defined operating period.

Regular maintenance and inspection of the automatic door by trained personnel authorized by the manufacturer provides the best guarantee for a long service life and an error-free operation.

We recommend the conclusion of a service contract with the respective service department in your region.

Operator Duties

According to principles for inspecting automatic door systems, in particular according to case law of safety obligations, automatic door systems must be inspected by a qualified technician before commissioning and thereafter according to the manufacturer recommendation. It is particularly important for the protection of people, to observe and to comply with the requirements for public access facilities! The operator is responsible to fulfill the duties required for the door system.

Maintenance and Inspection Schedule

Schedule of tasks, responsibilities, and recording requirements
Task To be conducted by Time of implementation Entry in log book required
Final inspection Technical expert After ready for use installation of the door system Yes
Maintenance and cleaning
(especially of the sensors for protection and tripping)
Operator Weekly or if required No
Function and safety check Operator Monthly No
Regular maintenance Technical expert 1 × per year, or according to country specific directives and regulations Yes
Regular testing (inspection) Technical expert 1 × per year, or according to country specific directives and regulations Yes
Regular testing (inspection) for door systems in escape route Technical expert 2 × per year, or according to country specific directives and regulations Yes
Regular testing of fire doors Technical expert 1 × per year, or according to country specific directives and regulations Yes
Regular functional testing of lock for holding door open Operator 1 × per year, or according to country specific directives and regulations No
Regular testing of lock for holding door open Technical expert 1 × per year, or according to country specific directives and regulations Yes
Regular maintenance of lock for holding door open Technical expert 1 × per year, or according to country specific directives and regulations Yes