11 Parameterization

After carrying out a teach-in run, the operator can be operated with the basic parameters. The system offers the option to adapt the travel parameters to the actual conditions as well as to activate advanced functions. These parameters should be set during commissioning according to the customer’s wishes.

11.1 Change parameters

Fig. 102: Parameter adjustment interface
  1. Press enter/menu for 3 seconds to open the parameters menu.
  2. Use up or down to select the parameter to be changed.
  3. Press enter to display the parameter value.
  4. Press select to select the parameter value to be changed.
    The value flashes.
  5. Or press up/down to change the parameter value.
  6. Press enter to save the changed parameter value.
  7. Press back to return to the parameters menu.
  8. Repeat steps 2-7 to change more parameters.
  9. If all parameters have been set, press exit to exit the parameters menu.

11.2 Parameter overview

The parameters described here can be set via the keypad on the control unit. Further settings can be activated via the OSI or TMS-Soft.

If a parameter only applies to certain operator systems (Standard, CO 48 or FST operator), the parameter is labelled accordingly in the table.

Dorma ES 250/400 PRO Parameters
Parameter Display Value range / unit Values (default = bold) Explanation
Number of door leaves 1-2 1 1-leaf
2-leaf (2)
Set the number of door leaves.
Power supply type 1-2 1 180 W power supply unit (1)
130 W power supply unit (2)
Select power supply unit type.
Operator locking device
(Standard and CO48 operator)
0/1/4/5 0 None (0)
Standard locking device (1)
Fail-safe locking (4)
Fail-secure locking (5)
Configure locking device type.
Operator locking device
(FST operator)
0-2 0 None (0)
Standard locking device (1)
FIA locking device (2)
Configure FST operator locking.
Door lock 0-2 0 None (0)
Combination lock (1)
RC3 locking device (2)
Select door lock type.
Program mode
(Standard and CO 48 operator)
0-2 0 Standard (0)
CO48-connect (1)
Fire protection function (2)
Set program mode.
Program Mode
(FST operator)
0-1 0 FST (0)
FIA (1)
Set FST program mode.
Operating mode switch type 0-4 0 Conventional PGS (0)
EPS-CAN (1)
TMS Soft only (2)
DPI/OSI only (3)
EPS-CAN/TMS-Soft/DPI/OSI (4)
Select switch type for operating mode.
Battery mode 0-3 0 No battery (0)
Emergency close (1)
Emergency open (2)
Emergency operation (3)
Configure battery backup behavior.
Acceleration in open direction 0–9 7 0 to 9 Adjusting the acceleration in open direction.
Opening speed
(Standard and CO48 operator)
10-90 cm/second 50 Setting the opening speed.
Opening speed
(FST operator)
*-90 cm/second 65
*) depends on door leaf weight and size
Setting the opening speed for FST.
Force limitation in open 5-31 10 N 15 Setting the force limitation in opening direction.
Hold-open time 0-180 seconds 1 Setting the hold-open time.
Night/bank hold-open time 0-180 seconds 0 Setting the hold-open time for night/bank.
Closing speed 10-90 cm/second 25 Setting the closing speed.
Force limitation in closed position 5-31 10 N 15 Setting the force limitation in the closing direction.
Sensitivity of collision detection (undershot) 0-2 0 Low sensitivity (0)
Medium sensitivity (1)
High sensitivity (2)
Sensitivity when threshold value is undershot.
Sensitivity of collision detection (exceeded) 0-2 0 Low sensitivity (0)
Medium sensitivity (1)
High sensitivity (2)
Sensitivity when threshold value is exceeded.
Locking force 0-9 10 N 6 Setting the locking force.
SiAK sensor test 0-8 0 Off (0)
SCE (high active) (1)
MCE (high active) (2)
SCE + MCE (high active) (3)
SCE (low active) (4)
MCE (low active) (5)
SCE + MCE (low active) (6)
SCE (hi) + MCE (lo) (7)
SCE (lo) + MCE (lo) (8)
Configure sensor testing logic.
Multiport default setting 0-4 0 User configuration (0)
Standard configuration (1)
Status configuration (2)
Pharmacy configuration (3)
Set default configuration profile.
Synchronous operation 0-2 0 Off (0)
Master (1)
Slave (2)
Configure synchronous operation mode.
Operating module 0-1 0 Disabled (0)
Active (1)
Enable or disable operating module.
COM 1 0-3 0 Off (0)
DPI/OSI (1)
TMS (2)
Data logger (3)
Configure COM 1 port.
COM 2
(only with COM Port Expander)
0-3 0 Off (0)
DPI/OSI (1)
TMS (2)
Data logger (3)
Configure COM 2 port.
Factory settings setup 1-3 1 Reset config/travel (1)
Level 1/special functions (2)
Level 2/passwords/data (3)
Reset options for factory settings.
CAN reset 0-1 0 Activation (0)
Set value to 1 (1)
Reset CAN bus.
Sensors’ parameter transfers 0–9 0 - (0)
Sensor 1-8 Write params (1-8)
Write all from sensor (9)
Transfer sensor parameters (e.g., after replacement).
Door pilot reset 0-1 0 Activation (0)
Set value to 1 (1)
Reset door pilot.
Door weight - kg - Shows the taught-in door weight.
Maintenance date via control panel 0-1 0 Activation (0)
Maintenance reset (1)
Reset maintenance date.
Delete error memories 0-1 0 Set value for deletion to 1 Clear error memory.
Service mode 0-2 0 Not active (0)
Service Mode 1 (1)
Service Mode 2 (2)
Activate service modes.