Commissioning and Final Work - Record 16 STA / 16 STA-UL Manual

8.1 Preparation

  • Interrupt power supply with main switch or power plug.
  • Leave door leaves open approx. 1 m.
  • Check wiring according to general schematic diagram AS.E.016.001 (page 51).

8.2 Checking Settings

  • Position jumpers for the required function.
  • Check external jumpers for auxiliary units not connected, such as EMERGENCY STOP, HEA, ELS 1, ELS 2.

8.3 Switching on Power Supply and Calibration Run

  1. Switch on power supply.
  2. A calibration run is performed automatically when switching on the supply voltage for the first time or following a hardware reset.
    Note: The door checks the weight of door leaves during braking tests.
  3. The door parameters are determined during the first 3 - 4 opening cycles.

8.4 Checking LEDs on the STG

Check LEDs 1, 2 and 4 - 7 according to the technical table (refer to page 38 of full manual).

8.5 Checking BDE Functions and Actuating Devices

BDE Position: Open

  • Door must open and remain open.
  • Check movement characteristics.
  • Door cannot be moved by hand when open.
  • Manual operation is obtained by pressing again; the door can then be moved freely.

BDE Position: Closed / Locked

  • Door must close.
  • Check movement characteristics.
  • Check locking if present (refer to status messages for wrong behavior).
  • Pressing initiates an SSK opening.
  • SSK must release (if present).
  • AKI and AKA must not operate.

BDE Position: One-Way

  • AKI and SSK must operate.
  • AKA must not be triggered when door is closed.

BDE Position: Automatic with Reduced Opening

  • AKI, AKA and SSK must operate.
  • Check reduced opening width.
  • Press: door opens to reduced width.

8.6 Programming Door Speeds and Hold-Open Times

These functions are described in Chapter 3rd Level (Programming Level) on page 42.

8.7 Configuration of Specific Customer Settings

The possibilities are described in application information 16.770. All modifications must be entered on the configuration sheet (situated in the operator).

8.7.1 Configuration for UL 325 Installations

In the 5th configuration level, the configuration "STA 16 UL" must be activated. For details see application information 16.770.

LED Configuration Settings (V 2.2)
Function Code (5 bits) Description
Factory setting (Default) 0 1 1 0 1 STA 16 UL not activated (LED 1=on)

8.8 Checking Safety

  • Set BDE position.
  • Open door (e.g., with AKI).
  • Cover a photocell (ELS) while closing. Door must re-open.
  • The same check must be performed if a 2nd ELS or another safety device is present.

8.9 Checking Automatic Reverse

  • Obstruct door while closing: Door must reverse. When the door next closes, it moves at creep speed past the obstruction point.
  • Obstruct the door while opening: Door stops for hold-open time and closes. When the door next opens, it moves at creep speed past the obstruction point.

8.10 Checking BAT Functions

Status 13 must be indicated on the BDE-E when removing the battery connection J7. If not indicated, jumper J13 is not at position 1 - 2 (see page 11).

8.11 Casing

With an F-dimension > 3,500 mm, 2 more multi-headers (016.007.000) must be fitted (total 4) to support the casing.

Fitting Casing

  • Divide the casing into lengths, screw together, use snap-in fastener and brush seal P1344.
  • Insert white hinge piece on casing P1341.
  • Push-in/engage casing.
  • Align casing.
  • Fit side covers if necessary.
  • Close casing and check for perfect setting.

8.12 Casing Version with Suspended Ceiling

(Refer to specific diagrams for suspended ceiling installation)

8.13 Fitting Internal Radar

  • Fit radar on casing with the aid of the drilling template or fit built-in radar.
  • Check radar settings inside and outside.

8.14 Handing Over to Customer

  • Ensure commissioning has been performed correctly according to this list.
  • The system should be handed over to the customer.
  • The functions and safety instructions must be explained with reference to the operating instructions.
  • The customer should be given a copy of the operating instructions.