Chapter 3: Technical Data
3.1.5 Integrated Functions
| Parameter | Function | Setting Range / Value | Description |
|---|---|---|---|
| dd | Hold open time (Automatic opening) | 0 to 30 s (Optional 0-180 s) | Adjusts the duration the door remains open. |
| dn | Hold open time (Night / Bank) | 0 to 30 s | Hold open time for night or bank mode. |
| do | Hold open time (Manual opening) | 0 to 30 s | Hold open time when door is manually opened. |
| hd | Door blocking behavior | Automatic, Manual | Controls how the door reacts to blocking (Door modes). |
| Ud | Electric strike delayed opening | 0 to 4 s | Delay for locking mechanism before opening. Feedback via X3 (43, 3). |
| Fo, Fc | Wind load control (Motor lock) | Max 33.7 lb f (150 N) | Voltage independent braking circuit. |
| CC | Cycle counter | 0 to 1,000,000 | Displays total door cycles. |
| hA, hF, hS | Power assist function | - | Drive support for manual opening of the door. |
| PG | Push & Go function | - | Automatic opening of the door at 4° open. |
| Sr | Door status | X7 (97, 98, 99) | Signals: Door closed, Door open, Door closed & locked (Com, N.O., N.C. contacts). |
| d2 | Night-bank (Key switch) | X1 (35, 3) | Configure for N.O. or N.C. contact. |
| d1 | Deactivation of drive function | X6 (4, 4a) | Configure for N.O. or N.C. contact. |
Additional Features
- User Interface: 4 button keypad, 2 digit display.
- Slot for upgrade cards: Extension of functional range (e.g., Firmware update).
- TMP: Temperature Management Program (Overload protection).
- IDC: Initial Drive Control (Driving phase optimization).
3.1 ED50/ED100/ED250 Operator Technical Data
3.1.1 Operating Conditions
- Ambient Temperature
- 5 to 122 °F [-15 to 50° C]
- Environment
- Suitable for dry rooms only
- Relative Air Humidity
- 93% maximum, non-condensing
- Power Supply
- 115 Vac ±10%, 50/60 Hz, 6.6 A maximum
- Branch Circuit Protection
- 15 A maximum, dedicated branch circuit (provided by others)
- Protection Class
- NEMA 1 [IP20]
- Power Wiring
- Black, white, bare copper (ground). 12 AWG maximum. Maximum wire size 16 AWG at connector plug.
- Operating Noise
- Maximum 50 db(A)
3.1.2 General Specifications
- Operator Dimensions
- 27" x 2 3/4" x 5 1/8" [685 x 70 x 130 mm] (W x H x D). 27" cover standard.
- Operator Weight
- 21.8 lb [9.9 kg]
- Power Supply for Accessories
-
ED100/ED250: 24 Vdc ± 5%, 1.5 A
ED50: Separate power supply required. - Max. Door Opening Angle
- 95 to 110° depending on installation type.
3.1.3 Inputs & 3.1.4 Outputs
- Activation Inputs (X4): Interior, exterior (N.O. contact). Wire size 14 AWG max.
- Safety Sensors (X5): Swing, approach sides (24 Vdc).
- Night-bank (Intecom system) (X10): Terminals 57, 57a (8-24 Vdc/Vac +5%).
- Deactivation of drive function (X6): Terminals 4, 4a (d1 parameter).
- Door Status (X7): Terminals 97, 98, 99 (Sr parameter).
3.3 Operating Specifications – ED50
| Maximum Power Consumption | 120 watts |
|---|---|
| Opening Force (Fo parameter) | Min: 4.5 lbf [20 N] | Max: 13.5 lbf [60 N] |
| Manual Closing Force (Fc parameter) | Min: 4.5 lbf [20 N] | Max: 13.5 lbf [60 N] |
| Maximum Door Weight | 220 lb [100 kg] (Depends on door width and application) |
| Door Width | Min: 28" | Max: 48" |
| Max. Opening/Closing Speed | 27 °/s (May be limited by door weight after learning cycle) |
| Reveal Depths | Pull arm with CPD lever: 0 to 2 1/4" [0 to 57.1 mm] Standard push arm: 0 to 11 13/16" [0 to 300 mm] |
3.2 Operating Specifications – ED100 / ED250
| Feature | ED100 | ED250 |
|---|---|---|
| Maximum Power Input | 120 watt | 240 watt |
| Max Door Weight (FE - Full Energy) | 250 lb [113 kg] | 320 lb [145 kg] |
| Max Door Weight (LE - Low Energy) | 600 lb [272 kg] | 700 lb [318 kg] |
| Door Width | 28" - 55" [700 - 1400 mm] | 28" - 63" [700 - 1600 mm] (Fire protection: max 55" / 1400 mm) |
| Opening Speed (0 - 90°) | 4* – 12 seconds | 3* – 12 seconds |
| Closing Speed (90 - 0°) | 5* – 21 seconds | 4* – 21 seconds |
| Axle Extensions | 20/30/60 mm | 20/30/60/90 mm |
| Reveal Depth (Pull Arm) | ± 1 1/16" [± 30 mm (-60 mm)] | |
| Reveal Depth (Push Arm) | 0 - 19 11/16" [0 - 500 mm] | |
* Depending on door panel weight, automatically limited with low energy power operator doors (ANSI A156.19). Maximum speeds will only be reached in full energy operating mode, low door panel weight, and a minimum learned opening angle of 95°.
3.4 Torque Overview; ED100 / ED250
3.4.1 ED100
| Parameter | Pull Version (Hinge Side) | Push Version (Opposite Hinge Side) | ||
|---|---|---|---|---|
| Min (EN 2) | Max (EN 4) | Min (EN 2) | Max (EN 4) | |
| Manual closing torque: ft lb [Nm] | 9.6 [13] | 27.3 [37] | 9.6 [13] | 27.3 [37] |
| Automatic closing force lb f [N] | 4.5 [20] | FE 34 [150] / LE 15 [67] | 4.5 [20] | FE 34 [150] / LE 15 [67] |
| Manual opening torque: ft lb [Nm] | 22 [30] | 37 [50] | 26 [35] | 40.6 [55] |
| Automatic opening force lb f [N] | 4.5 [20] | FE 34 [150] / LE 15 [67] | 4.5 [20] | FE 34 [150] / LE 15 [67] |
| Opening force of power-assist: lb f [N] | 5.2 [23] | 5.2 [23] | 5.2 [23] | 5.2 [23] |
3.4.2 ED250
| Parameter | Pull Version (Hinge Side) | Push Version (Opposite Hinge Side) | ||
|---|---|---|---|---|
| Min (EN 4) | Max (EN 6) | Min (EN 4) | Max (EN 6) | |
| Manual closing torque: ft lb [Nm] | 19 [26] | 48 [65] | 19 [26] | 66 [90] |
| Automatic closing force lb f [N] | 4.5 [20] | FE 34 [150] / LE 15 [67] | 4.5 [20] | FE 34 [150] / LE 15 [67] |
| Manual opening torque: ft lb [Nm] | 40.6 [55] | 63 [85] | 44 [60] | 66 [90] |
| Automatic opening force lb f [N] | 4.5 [20] | FE 34 [150] / LE 15 [67] | 4.5 [20] | FE 34 [150] / LE 15 [67] |
| Opening force of power-assist: lb f [N] | 5.2 [23] | 5.2 [23] | 5.2 [23] | 5.2 [23] |
NB: In the push version of the slide channel installation type, the forces reduce by approximately 33%.
Torques marked with ** are available in the event of an automatic opening in automatic mode.
Chapter 4: Terminal Board Interfaces
4.1 ED50/ED100/ED250 Terminal Board Interfaces
Tips and Recommendations:
- Use documentation provided with each device for electrical installation.
- It is recommended not to connect system accessories to board until operator has been commissioned and learning cycle performed.
Indicator LEDs & Components
- Green LED
- Status indicator.
- Yellow LED
- Maintenance / Status indicator.
- Red LED
- Error / Status indicator.
- Jumpers
- Factory installed at terminals 4 & 4a (Deactivation), 15 & 3 (Activation), 11 & 3. Remove if activation input is used.
- Upgrade Cards
- Slots available for DCW upgrade card and Fire protection upgrade card.
Terminal Connections Overview
| Terminal ID | Function | Description / Spec |
|---|---|---|
| X3 | Locking Device | Feedback (43, 3), Locking relay output (Motor lock provided by others). Max: 1A, 48 V DC/AC. |
| X4 | Activation Inputs | Interior, Exterior (N.O. Contact), 24V. |
| X5 | Safety Sensors | Swing side, Approach side. |
| X6 | Deactivation | Terminals 4, 4a. Connect Emergency Close, Smoke Detectors. |
| X7 | Door Status | Terminals 97, 98, 99. Relay output. |
| X8 | Output | 24 VDC Class II. Max current load: 1.5A. |
| X10 | Night-bank | Intercom system input (8-24 AC/DC). |
| X11 | Program Switch | Mode, Exit Only switches. |