The operator is ready for operation with basic parameters as soon as the learning cycle has been performed successfully. The system also enables you to adapt the driving parameters to the prevailing conditions and to activate extended functions. It is advisable to adapt these parameters to the customer's requirements during the commissioning of the system.
Navigation Instructions:
For control unit interface:
< 3s: Quit
> 3s: Reset
LEARN (> 8s): Fact-Setup
PRG (> 3s): Enter Programming Mode
For control unit interface:
< 3s: Quit
> 3s: Reset
LEARN (> 8s): Fact-Setup
PRG (> 3s): Enter Programming Mode
Configuration Parameters
| Parameters / Display | Range / Unit / Factory Setting | Explanation |
|---|---|---|
| Way of mounting |
Range: 0 to 1 Factory: 0 |
0: Lintel mounting on hinge side with slide channel, pull-version. 1: Lintel mounting on opposite hinge side with standard arm, push-version. |
| Lintel depth |
ED 100: -3 to 30 ED 250: -3 to 50 Factory: 0 |
The lintel depth is adjusted in steps of 10 mm. Consider the installation drawings to find the required dimension. |
| Door-leaf width |
ED 100: 7 to 11 ED 250: 7 to 15 Factory: 10 |
The rebate is included in the door-leaf width. The door width is indicated in steps of 100 mm. |
| Door type |
Range: 0 to 4 Factory: 0 |
0: Single-leaf door 1: Double-leaf door, active leaf, with rebate (overlapping) 2: Double-leaf door, passive leaf, with rebate (overlapping) 3: Double-leaf door, active leaf, without rebate 4: Double-leaf door, passive leaf, without rebate |
Driving Parameters and Functions
| Parameters / Display | Range / Unit / Factory Setting | Explanation |
|---|---|---|
| Opening speed |
ED 100: 8 to 50 ED 250: 8 to 60 Unit: Degrees/Second Factory: 25 (Reduces to 25°/sec in Low-Energy Mode) |
The opening speed refers to Automatic mode. Abide by country-specific limits and check after adjustment. The full adjustable range is only available when the Upgrade Card Full-Energy is installed. An internal monitoring function checks if the selected adjustments are admissible. |
| Closing speed |
ED 100: 8 to 50 ED 250: 8 to 60 Unit: Degrees/Second Factory: 25 (Reduces to 25°/sec in Low-Energy Mode) |
The closing speed refers to Automatic mode. Abide by country-specific limits and check after adjustment. The full adjustable range is only available when the Upgrade Card Full-Energy is installed. |
| Hold-open time |
Range: 0 to 30 (0 to 180 with Upgrade Card Professional) Unit: Seconds Factory: 5 (min. 5s for Low-Energy) |
Adjust the hold-open time so that users have sufficient time to pass the door system. The hold-open time starts as soon as the contact/voltage at the activator inputs opens/drops. A minimum of 5s is required for Low-Energy Mode. |
| Night-/Bank hold-open time |
Range: 0 to 30 Unit: Seconds Factory: 10 |
The Night-/Bank hold-open time (key switch) can be adjusted separately. It starts when the contact at the Night-/Bank activator input is opened and the door is open. |
| Wall blanking on hinge side |
Range: 60 to 99 (99 = disabled) Unit: Degrees Factory: 80 |
When the door reaches the adjusted angle, the system will ignore incoming signals from the safety sensor on the hinge side. Required if the door opens against an obstacle. Establish the smallest possible area for safety. |
| Safety sensor test |
Range: 0 to 6 Factory: 0 |
0: Test off (Required for IRS-2). 1: Sensor test on hinge side – high active 2: Sensor test on opposite hinge side – high active 3: Both sides – high active 4: Sensor test on hinge side – low active 5: Sensor test on opposite hinge side – low active 6: Both sides – low active |
| Activation via safety sensor on opposite hinge side |
Range: 0 to 1 Factory: 0 |
0: System ignores signals when door is closed. 1: Safety sensor can trigger an opening pulse while the door is closed. |
| Delayed opening for locking mechanism |
Range: 0 to 40 (steps of 10ms) Unit: 100 ms (implied by text logic, commonly steps) Factory: 4 |
The delay starts as soon as the system has been activated. The door opens on expiry of the time. If "0" and input bridged, no "pulling before opening". |
| Ease of preload prior to unlocking |
Range: 0 to 9 Factory: 0 |
Force with which the door is pushed in closing direction before it opens to relief electric strike. Higher force = higher strain on arm fixing; adjust as low as possible. |
| Static force in opening direction |
Range: 2 to 15 (reduced in Low-Energy) Unit: 10 N per step (approx) Factory: 6 |
Adjust forces impacting on the closing edge. Basic parameter for wind load control. Verify actual force with measurement to ensure compliance with standards. |
| Static force in closing direction |
Range: 2 to 15 (reduced in Low-Energy) Unit: 10 N per step (approx) Factory: 6 |
Adjust forces impacting on the closing edge. Basic parameter for wind load control. Verify actual force with measurement. |
| Latching action |
Range: 0 to 9 Factory: 0 |
Motor-driven latching action to overcome seals/locks. Increase step by step to avoid damage. Ensure fixings are suitable. |
| Angle of latching action |
Range: 2 to 10 Unit: Degrees Factory: 3 |
Determines the opening angle at which the motor-driven latching action is activated. |
| Keep-closed force |
Range: 0 to 9 0 = off, 1-9 = on Factory: ? (Not specified clearly, text says adjustable) |
Designed to keep the door in its "closed" position against wind. |
| Push & Go |
Range: 0 to 1 Factory: 0 (off) |
0: off 1: on Triggers automatic opening when door is moved manually by 4° from "closed". "hd" (door closer mode) must be 0. |
| Program switch type |
Range: 0 to 2 Factory: 0 |
0: Internal program switch activated. 1: External program switch connected. 2: External DCW program switch connected. |
EPS DCW & Logic Functions
| Parameters / Display | Range / Unit / Factory Setting | Explanation |
|---|---|---|
| Behaviour following a power reset |
Range: 0 to 1 Factory: 0 |
0: Returns to previously adjusted function. 1: Automatically switches to OFF position (insurance-compliant locking). |
| Internal program switch – delayed activation |
Range: 0 to 1 Factory: 0 |
0: Immediate activation. 1: 10-second delay. Reasonable if user must pass door and detectors after adjustment. |
| Unlocking during business hours |
Range: 0 to 1 Factory: 0 |
0: Door locked in "closed" position. 1: Door does not lock in "closed" position in Automatic Function. Requires 100% duty electric strike. |
| Function of status relay |
Range: 0 to 3 Factory: 1 |
0: Deactivated. 1: Switched at "closed" position. 2: Switched at "open" position. 3: Malfunction output. |
| Triggering hold-open by closing door leaf |
Range: 0 to 1 Factory: 0 |
0: De-activated (manual pushbutton required). 1: Activated (manually moving 10° triggers hold-open). |
| De-activation of operator (contact setting) |
Range: 0 to 1 Factory: 0 |
0: NC contact (De-activated while open). 1: NO contact (De-activated while closed). |
| Night-/Bank Function (contact setting) |
Range: 0 to 1 Factory: 0 |
0: NO contact (Triggered while closed). 1: NC contact (Triggered while open). |
Diagnosis
| Parameters / Display | Range / Unit / Factory Setting | Explanation |
|---|---|---|
| Cycle counter |
0 to 99 Unit: 10,000 cycles |
Displays cycles in steps of 10,000 (e.g., 4 = 40,000). 99 = 990,000+. Exact number via hand-held terminal. |
| Deletion of error log |
Range: 0 to 1 Factory: 0 |
1: Deletes error log, then auto-resets parameter to 0. |
| Reset of service interval display |
Range: 0 to 1 Factory: 0 |
1: Resets service counter to 200,000 cycles / 12 months. |
| Level of factory settings |
Range: 1 to 2 Factory: 1 |
1: Standard Factory Settings (Upgrade cards valid). 2: Extended Factory Settings (Deletes upgrade cards). |
| Opening angle |
Range: 0 to 110 Unit: Degrees |
Displays the adjusted opening angle from learning cycle. Only adjustable via learning cycle. |
| Door closer / Automatic Mode |
Range: 0 to 1 Factory: 1 (Door closer mode) |
0: Automatic Mode (Wind load, Push & Go available). 1: Door closer mode (Power Assist available). |
| Activation angle for Power Assist Function |
Range: 1 to 5 Unit: Degrees Factory: 3 |
Lower value = more sensitive response. |
| Power Assist Function (force adjustment) |
Range: 0 to 10 Factory: 0 |
Higher value = easier to open manually. 0 = de-activated. Only available in door closer mode. |
Upgrade Cards & Miscellaneous
| Parameters / Display | Range / Unit / Factory Setting | Explanation |
|---|---|---|
| Upgrade Cards Status | 0 to 3 |
0: Not available. 1: Available, not activated. 2: Activated. 3: Removed. (Applies to Fire protection, Full-Energy, Professional, etc.) |
| Configuration of COM1 interface |
Range: 0 to 2 Factory: 0 |
0: Operation via hand-held terminal. 1: DORMA debugging service. 2: DORMA remote service. |
| Backcheck when door is opened by hand |
Range: 5 to 20 Unit: Degrees Factory: 10 |
Angle from which door is decelerated when opened by hand. Value deducted from opening angle. |
| Thickness of door |
Range: 0 to 800 Unit: mm Factory: 35...80 |
Influences measured opening angle. Enter exact thickness for detail. |
| Castor angle for double-leaf doors |
Range: 0 to 30 Unit: Degrees Factory: 30 |
Angle active leaf must reach before passive leaf starts opening. |
| Hinge clearance |
Range: +5 to -5 Factory: 3 |
Determines door angle. Original setting "3" for 30 mm. Center-pivoted doors need negative value. Requires learning cycle after change. |