15.1 Entering the program mode (classification)
- Disconnect the mains plug.
- Press and hold the LEARN BUTTON while connecting the mains plug.
- Watch the ERROR LED.
- Release the LEARN BUTTON after the second 5s interval has passed.
15.2 Identify the current classification
The ERROR LED flashes an amount of short flashes that correspond to the classification number. After a short pause, the LED will repeat the classification number and so on.
15.3 Changing the classification
If you push the LEARN BUTTON once, the classification number will increase. When you have reached the highest classification number it will start at number one again.
- Push the button until you get the requested classification.
- Disconnect the mains plug.
Next time you connect the mains, the operator will use the new classification.
15.4 Classification table
| Classification | Low energy | Full power |
|---|---|---|
| Standard | DIN 18650-2 (Default) | Standard |
| Opening speed | Automatic limitation (3-12 s) | 2.5 - 12 s |
| Closing speed | Automatic limitation (4-12 s) | 4 - 12 s |
The fastest setting of Opening Speed and Closing Speed are automatically limited to the value in the table, and can only be reduced.
If classification 2 (Low energy) is used, the operator will automatically follow the speed limitation in DIN 18650-2.
The learn procedure must be carried out after a change of the classification setting.
Speed settings for Low energy mode
The table shows minimum opening time to back check or to 80° open, or minimum closing time from 90° to 10° open.
| Width of door leaf (mm) | Door mass (kg) | ||||
|---|---|---|---|---|---|
| 90 | 80 | 70 | 60 | 50 | |
| 750 | 3.5 | 3.3 | 3.2 | 3.2 | 3.0 |
| 850 | 3.6 | 3.4 | 3.2 | 3.1 | 3.1 |
| 1000 | 4.2 | 4.0 | 3.7 | 3.4 | 3.2 |
| 1200 | 5.1 | 4.8 | 4.5 | 4.2 | 3.8 |