Process for Changing Parameters
- Disconnect batteries if any.
- Disconnect the electrical power contact.
- Press the LEARN BUTTON (LRN) and keep it depressed.
- Connect the electrical power contact.
- Watch the ERROR LED.
- Release the LEARN BUTTON after the 5 seconds (LED is out). The ERROR LED flashes a number of short flashes that corresponds to the parameter group number (see table). After a short pause the LED will repeat the group number, and so on.
- Pushing the LEARN BUTTON once, increases the parameter group number. When the highest parameter group number is reached it will start with number 1 (default) again.
- Push the button until you get the requested parameter group. Ensure that the requested group of parameters has been selected by counting the number of flashes.
- Disconnect the electrical power contact.
- Next time the electrical power is connected, the operator will use the new group of parameters.
Parameter Groups Overview
| Parameter / Group | 1 (Default) | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 |
|---|---|---|---|---|---|---|---|---|---|---|
| Open/Close Hold Open Time | 15 min | Infinite | 15 min | 15 min | 15 min | 15 min | 15 min | 15 min | 15 min | 15 min |
| Battery Mode | Power save | Power save | Convenience | Power save | Power save | Convenience | Power save | Power save | Power save | Convenience |
| Locked During Kill | Yes | Yes | Lock follows prog. selector | Yes | Yes | Yes | Yes | Lock follows prog. selector | Yes | Yes |
| Obstruction Mode | Door closer | Door closer | Door closer | Door closer | Reverses1 | Door closer | Door closer | Reverses1 | Door closer | Door closer |
| Other Settings | See full manual for Double Egress, Lock Retry, and Impulse specifics per group. | |||||||||
Note 1: If set to Reverses when obstructed, the operator re-opens when obstructed, similar to a presence impulse.
Note 2: In double door installations, for SLAVE this parameter will follow the parameter group chosen at the SLAVE, regardless of MASTER config.
14.1 Learn with Advanced Setting of “Back- and Latch-check”
See the prerequisites for performing a “learn” in section Auto-learn – automatically sets back and latch check (recommended).
- Push the button once as for auto-setting. Text 'LEARN' will show on the display. Same as for auto-setting.
- Stop the door at required open position.
- The door reverts towards closed position.
- Stop the door at required latch-check position.
- The door reverts to learn the back check.
- Stop the door at required back-check.
- Remove the stop.
- The door reverts to closed position.
14.2 Revert to Default Values for “Back- and Latch-check”
- Disconnect batteries if any.
- Disconnect the electrical power contact.
- Press the LEARN BUTTON and keep it depressed.
- Connect the electrical power contact.
- Watch the ERROR LED.
- Release the LEARN BUTTON after 3 seconds (LED is out).
- The BACK CHECK, LATCH CHECK and OPEN POSITION have now reverted to default values.
- Disconnect the electrical power contact.
- Next time the electrical power is connected, a new learn is needed to be run, and the operator will use the default values.