Process for Changing Parameters

  1. Disconnect batteries if any.
  2. Disconnect the electrical power contact.
  3. Press the LEARN BUTTON (LRN) and keep it depressed.
  4. Connect the electrical power contact.
  5. Watch the ERROR LED.
  6. Release the LEARN BUTTON after the 5 seconds (LED is out). The ERROR LED flashes a number of short flashes that corresponds to the parameter group number (see table). After a short pause the LED will repeat the group number, and so on.
  7. Pushing the LEARN BUTTON once, increases the parameter group number. When the highest parameter group number is reached it will start with number 1 (default) again.
  8. Push the button until you get the requested parameter group. Ensure that the requested group of parameters has been selected by counting the number of flashes.
  9. Disconnect the electrical power contact.
  10. Next time the electrical power is connected, the operator will use the new group of parameters.

Parameter Groups Overview

Table 1: Parameter Groups 1-10
Parameter / Group 1 (Default) 2 3 4 5 6 7 8 9 10
Open/Close Hold Open Time 15 min Infinite 15 min 15 min 15 min 15 min 15 min 15 min 15 min 15 min
Battery Mode Power save Power save Convenience Power save Power save Convenience Power save Power save Power save Convenience
Locked During Kill Yes Yes Lock follows prog. selector Yes Yes Yes Yes Lock follows prog. selector Yes Yes
Obstruction Mode Door closer Door closer Door closer Door closer Reverses1 Door closer Door closer Reverses1 Door closer Door closer
Other Settings See full manual for Double Egress, Lock Retry, and Impulse specifics per group.

Note 1: If set to Reverses when obstructed, the operator re-opens when obstructed, similar to a presence impulse.

Note 2: In double door installations, for SLAVE this parameter will follow the parameter group chosen at the SLAVE, regardless of MASTER config.


14.1 Learn with Advanced Setting of “Back- and Latch-check”

See the prerequisites for performing a “learn” in section Auto-learn – automatically sets back and latch check (recommended).

  1. Push the button once as for auto-setting. Text 'LEARN' will show on the display. Same as for auto-setting.
  2. Stop the door at required open position.
  3. The door reverts towards closed position.
  4. Stop the door at required latch-check position.
  5. The door reverts to learn the back check.
  6. Stop the door at required back-check.
  7. Remove the stop.
  8. The door reverts to closed position.

14.2 Revert to Default Values for “Back- and Latch-check”

  1. Disconnect batteries if any.
  2. Disconnect the electrical power contact.
  3. Press the LEARN BUTTON and keep it depressed.
  4. Connect the electrical power contact.
  5. Watch the ERROR LED.
  6. Release the LEARN BUTTON after 3 seconds (LED is out).
  7. The BACK CHECK, LATCH CHECK and OPEN POSITION have now reverted to default values.
  8. Disconnect the electrical power contact.
  9. Next time the electrical power is connected, a new learn is needed to be run, and the operator will use the default values.