Record DFA127 Quick Start Manual & Setup Instructions

Guide to Blue Button on the Master Processor

The blue button on the master processor supports multiple uses (MF) depending on the number of flashes:

Number of Flashes Operation Level / Result
1 Single Impulse – Opens Door
3 Learns door parameters (Calibration Run)
4 Programming mode
6 Spring Calibration run on the DFA 127 – Before connecting Arm
8 Factory standards reset
9 Full Reset - 9 flashes and then pull the emergency stop OUT then IN
14 Soft reset (the same as pressing the Record Logo)

BDE – Control Switch Operations

The control switch supports multiple operating states:

  • Hold Open
  • Manual Operation
  • No Entry
  • 2-Way Automatic
  • Locked / Closed
Note on Locking: When the lock symbol is showing, it represents that the key lock is ON. Ensure you understand how both locking and unlocking the keypad operate.

How to Reset the Operator & Door

  1. Press and hold the Record logo for 10-13 seconds.
  2. The message “DFA127 Software Version” will flash up, followed by the option to reset: Yes / No.
  3. Upon selecting Yes, the doors will move to the closed position and reset.
  4. After 3 seconds, activate the doors so they go through one learn cycle of open/close (moves slowly) to complete their reset cycle.

Final Exit Procedure

For the final exit out of the building, place the program selector into the Locked function. When you are ready to leave, press the lock symbol once to give a single open/close exit.

Important: Once outside, stand clear of the sensors. After the doors are closed, set your manual locks. Remember to unlock manual locks prior to using the first entry key switch on the outside of the building.

Electric Lock Wiring Guidelines

Terminals used for electrical connection:

  • 19: 0V
  • 20: N/O (Normally Open)
  • 21: COM (Common)
  • 22: N/C (Normally Closed)
  • 23: VAK
  • 14: 24VDC

Lock Configuration: Electric Strike or Mag Lock

  • Fail Safe: Use terminal 20 (N/O)
  • Fail Secure: Use terminal 22 (N/C)

Select the locking function and lock type depending on what lock type is connected and your specific requirements.

Caution: The VRR Relay is rated at 1 amp maximum load.

BDI-M Set up

To configure the door to lock on electric mags when the closed position is selected on the key switch, you need to change the setting in the control panel menu to LOCK-A.