Record DFA127 Automatic Door Parameter Setup Guide

DFA127 Quick Start Manual - Parameter Settings

1. Driving Cycle

Parameter Setting Range Factory Default Description
Closing speed 0 - 40 (5 – 20 s) 18 Slider control with 40 steps
Opening speed 0 - 40 (3 - 20 s) 36 Slider control with 40 steps
Acceleration 0 – 40 (40 = max.) 36 Influences the start-up behaviour while opening and closing
Latch check 0 – 40 0 Earlier slow-down while closing elongates the length of run with minimal possible closing speed in the area of the last 20° (e.g. safeguarding against shearing edge)

2. Time Delay Open

Parameter Setting Range Factory Default Description
Time delay open 0 – 40 (0 – 60 s) 2 Effective with AKA, AKI and push to actuate
0 – 20: Steps of 1 s
21 – 40: Steps of 2 s
Time delay SSK 0 – 40 (0 – 60 s) 4 Effective with SSK
0 – 20: Steps of 1 s
21 – 40: Steps of 2 s

3. Drive

Parameter Setting Range Factory Default Description
Opening angle 0 – 40 35 The opening angle is estimated during the calibration run and is equivalent to the value of 40
Collision 0 – 40 20 Influences the force for the reversing.
0: weak
40: strong
Brake Without
Closing position
Opening position
Open/closed position
Without No brake integrated or no brake wanted. Or holding brake options for open/closed states.
Types of arms Standard arm
Sliding pulling
Sliding pushing
Inheader
Standard arm Standard arm for pushing opening / Sliding arm for pulling opening / Sliding arm for pushing opening / Special application (for USA only)
Inverse Disabled / Enabled Enabled Opening of the door by spring tension in case of power failure.
Spring type Display only EN 4 Springiness value is estimated during calibration run (MF 6. light pulse).
Control with FPC 902:
EN 4: 35-41
EN 5: 42-59
EN 6: 60-89
Display Unknown if out of range.
Limit open Disabled / Enabled Disabled Enabled: The door hold is stronger in the open position.

4. Entrance System

Parameter Setting Range Factory Default Description
Fire alarm Disabled / Enabled Enabled Enabled: specific adaptation for the requirement of the EN-norms for fire doors.
Control Single control
Master control
Slave control
Single control This setting is effected automatically under operating conditions. Simulation or Master/Slave-Control can be set with the FPC 902.
Interlock type Without interlock Without interlock Function not yet integrated
Door type Basic operator
USA
USA Low Energy
UK
UK Low Energy
Basic operator Frequently-used door types can be chosen for specific applications.

5. Master/Slave 2 Door Leaves

Parameter Setting Range Factory Default Description
Function AKA Master + Slave
Master only Entry
Master + Slave AKA is effective on both operators, or only master operator while AKI/SSK operate on both.
Overlap 0 - 40 5 Only one door leaf moves in the pre-set overlap region. Stationary leaf waits during opening/closing.
Open sequence 0 - 40 5 Delayed start-up of the stationary leaf
Close sequence 0 - 40 20 Delayed closing of the moving leaf. (0 = synchronous activity).

6. Manual Control

Parameter Setting Range Factory Default Description
During closing Disabled / Enabled Disabled Enabled: The door closes motor-guided only with spring tension.
When locked Disabled / Enabled Disabled Enabled: When locked, it can be opened manually without auto closing (night-watchman mode).
When automatic Disabled / Enabled Disabled Enabled: When in automatic mode, it can be opened manually without auto closing.
Collision Disabled / Enabled Disabled Enabled: If obstructed over 1s, it re-opens with motor force.
Support during closing Disabled / Constant / Cumulative / Final bang / Slowly, cumulative / Slowly, final bang Disabled Varying types of motor closing force adjustments during the last 2° - 10° of closing process.
Active sensors Disabled / SIS disabled / SIS enabled Disabled Controls active sensor configurations including or excluding SIS.
Closing speed 0 - 40 20 Slide control with 40 steps, depending on adjusted spring force.

7. Control Panel

Parameter Setting Range Factory Default Description
Mechanical panel (BDE-M) 3-digit (AUTO)
4-digit
3-digit (OFF-A)
3-digit (OFF-M)
3-digit (LOCK-A)
3-digit (LOCK-M)
3-digit (AUTO) Operational panel configurations for Manual, Automatic, Con. open, Locked and OFF switch combinations.
BDE-D (Language) Deutsch / Français / English / English US English Language for the text output
Keyboard Normal / OFF-Mode Normal Standard-Function or Special mode where Locked mode is replaced by OFF.
Contrast BDE 1 & 2 0 - 40 0 Contrast settings for respective BDE displays.
Light time 0 - 40 0 0: No backlight. 1-39: Backlight seconds. 40: Continuous.

8. Locking, Interlock, & I/O

Category Parameter Setting / Range Factory Default Description
LOCKING Locking function Normally locked / Always locked Normally locked Configures when VRR interlock is operated (permanently active vs lock button-based).
Lock type Standard / Locking bolt / Magnet / Pulse Standard Configuration for electronic lock type (e.g. eff-eff, motor-lock).
VRR manually Disabled / Enabled Disabled Approved for manually closed doors. Protects actuators based on lock reverse signal.
Start delay 0 - 40 (0 - 8 s) 0 Application for motor locks without reverse signal on VAK.
INPUT AUX1_IN Disabled / BEA Bodyguard Disabled Special safety function (USA only)
AUX2_IN AKA / Railbeam AKA Special function (USA only)
OUTPUT AUX1_OUT Disabled / BEA Bodyguard / Test sensors Disabled Special function, including safety sensors with integrated test input.
MISCELLANEOUS Push to actuate Disabled / Normal / Slow / Manually operated Disabled Configures motor reaction variables and wind pressure compensation behavior.