ED 100 / ED 250 Radar Sensor M A01: Setup & Error Codes

The Radar Sensor M A01 is the dedicated activation sensor for the ED 100 and ED 250 swing door operators: it detects approaching people, lets the control unit calculate the ideal opening time, and — thanks to targeted cross-traffic detection — keeps the door closed when people merely walk past. This guide condenses the official quick guide (060616-45532, 06/2024): mounting positions, DIP switches, CAN wiring, commissioning parameters and the complete LED error-code table.

Compatibility requirement: the M A01 is designed exclusively for ED 100/250 operators with firmware V2.9 or higher. All work described here may only be carried out by qualified electricians.

1. Technical data

Parameter Value
Supply voltage 24 V DC ±15%
Power consumption < 2.5 W
Operating temperature −20 °C to +55 °C
Rel. humidity up to 95%, non-condensing
Protection class IP54
Mounting height 2.0–4.0 m
Transmission frequency 24.050–24.250 GHz
Transmission power < 20 dBm
Detection speed min. 0.1 m/s
Detection area approx. 10 m

Compliance: Machinery Directive 2006/42/EC, EMC 2014/30/EU, Radio Equipment 2014/53/EU, RoHS 2011/65/EU; EN 16005:2013, EN 300 440, EN 301 489-1/-3, EN 62368-1 — plus UKCA for the UK market.

2. Mounting positions and heights

# Parameter Value
1 Installation height from the floor 2.0–4.0 m
2 Height above the door leaf upper edge (central mounting, recommended) 0.2–0.5 m
3 Recommended positions max. 0.8 m displacement from center permitted; 1-leaf: exactly centered above the leaf; 2-leaf: exactly centered above both leaves
4 Optional positions mounting at operator height above the hinges is permitted (preferably on the active leaf for 2-leaf doors) — note: on 2-leaf doors this increasingly leads to false alarms
Avoid shadowing: the ED operator housing must not block the sensor's field of view. Determine positions on both the hinge side and the opposite side centrally above the door.

3. DIP switch settings (before wall mounting)

Set the DIP switches before mounting the sensor on the wall, and observe ESD protective measures. If the DIP positions are changed later, a CAN reset (Cr = 1) is mandatory.

DIP ON OFF
1 outside detector inside detector
2 opposite side to the hinge hinge side
3 option option
4 CAN terminating resistor active — set on the last participant in the bus series terminating resistor inactive

4. Wiring and tilt angle

Connection terminals (color code): white = +24 V DC · green = CAN-H · yellow = CAN-L · brown = GND.

Critical: the M A01 connects to the CAN 1 terminal on the ED connection board CAN. The CAN 2 terminal is not compatible with the radar sensor — CAN 1 and CAN 2 are not interchangeable.
Mounting height 2.0 m 2.5 m 3.0 m 3.5 m 4.0 m
Recommended tilt angle (15° steps) 30° 30° 45° 45° 45°

For intermediate heights, use the tilt angle of the next higher or lower mounting height. In special cases (e.g. a wall inside the detection area) the angle may be adjusted. On 2-leaf doors, the ED connection board CAN goes into the active leaf operator.

5. Commissioning and parameters

Parameters are set via the handheld device ("Special functions" menu) or the ED's user interface. The CAN reset parameter is only available on the ED's user interface.

Trigger a CAN reset (Cr = 1) whenever: initial commissioning after all devices are connected · a device was added to the bus · a device was replaced · DIP switches were adjusted · the control unit no longer recognizes the CAN devices. The parameter resets itself to 0 afterwards. Note: with at least one M A01 connected, the CAN reset automatically sets the hold-open time dd to "0" (changeable afterwards). After a factory reset of the ED, all parameters — including C1 and the sensor parameters — must be set again.
Parameter Range Default Function
Cross-traffic mode inside / outside (MA01 IM QV / AM QV) 0–3 0 0 = hide cross-traffic left & right · 1 = capture right · 2 = capture left · 3 = capture both sides
Mounting height inside / outside (Ih / Ah) 20–40 25 sensor mounting height in 100 mm increments
Door opening time inside / outside (IT / AT) 0–6 3 0 = very early … 6 = very late; smaller values weaken cross-traffic suppression — the door opens more sensitively
So (opening speed) — — affects the general opening time: slower opening = door opens sooner; faster = opens later

6. Troubleshooting: the 7 LED error codes

The RGB LED on the ED connection board CAN indicates errors by its number of flashes; the highest-priority message is shown. Process data between the ED control unit and the radar sensor is not exchanged while an error is active.

No. Error Cause Fix
1 TMS communication error communication between ED control unit and ED connection board CAN interrupted check C1 parameter setting and the connection cable; if applicable reset the operator power supply
2 CAN initialization error sensor address assignment failed — expected responses not received check CAN cable and bus termination (DIP 4 = ON on the last participant); perform CAN reset
3 Unknown CAN bus participant unknown devices detected or max. number of participants exceeded check connected devices, remove incorrect ones from the bus; execute CAN reset
4 Device assignment error device positions appear twice in the assignment check DIP switch settings on the radar sensors; execute CAN reset
5 Missing device error a trained radar sensor is no longer available after switch-on check CAN cable and the device; if applicable reset the operator power supply
6 CAN communication error communication between radar sensor and ED connection board CAN interrupted check CAN cable; if applicable reset the operator power supply
7 Radar sensor error sensor sends an emergency message due to an internal error reset the ED operator power supply

Compatible sensors and CAN accessories for ED 100 / ED 250

DoorDynamic supplies OEM-compatible radar sensors, ED connection boards CAN, cables and accessories compatible with the dormakaba ED 100 and ED 250 — verified for firmware V2.9+ systems, with fast shipping to Europe and the Middle East. Tell us your error code or mounting situation, and we will help you identify the right part.

dormakaba, DORMA and other mentioned brand names are trademarks of their respective owners. DoorDynamic is an independent supplier of compatible parts and is not affiliated with the original manufacturer. All values in this article are taken from the public quick guide (060616-45532, 06/2024) and are provided for reference only.