Commissioning Instructions | Dorma ES 250 PRO & ES 400 PRO

Commissioning Instructions | Dorma ES 250 PRO & ES 400 PRO

7. Commissioning

7.1 Requirements

Before starting, ensure the following conditions are met:

  • The operator is mounted correctly, mechanically and electrically.
  • The area of movement of the door leaf is free from obstacles.
  • The door is in the half-open position.
  • The connections for the safety sensors on the extension module SiAK (optional) are bridged.
  • The operating mode switch is in Off mode.
  • An emergency stop or emergency open button, if present, is not pressed.

7.2 Safety during commissioning

7.3 Commission the operator

7.3.1 Service Mode

The system uses service modes to facilitate setup:

  • Service Mode 1: The sensors are not evaluated by the control unit.
  • Service Mode 2: The CAN components are not evaluated by the control unit.

If a Service Mode is activated, all errors are acknowledged and the closing movements run at crawl speed.

Initialization Procedure

  1. Power Supply Connection

    Plug in the mains plug to the power supply unit. If present, connect the battery.

    The control unit carries out a self-test.
    The device detection is shown on the 2-digit display. "ES" followed by the "control unit" (represented by XXX) and the "firmware version".

    Control unit codes:
    FST = escape route control unit
    STd = standard control unit
  2. Bus Initialization
    The CAN BUS is initialized.
    The small, spinning “o” and the “P” show that parameterization is required.
    The control unit switches to Service Mode 2.
Note: If a CAN synchronization cable is used, replace steps 3-7 with the commissioning instructions for the CAN synchronization cable.
  1. Open Parameters Menu

    Press for 3 seconds to open the parameters menu.

  2. Set Parameters

    Set the parameters “L1”, “dL” and “Pr”. (Refer to “11 Parameterization” in the full manual).

    If a mechanical operating mode switch is used, set the parameter “PS” to the value 0.

  3. Exit Parameters Menu

    Press to exit the parameters menu.

    The small, spinning “o” and the “O” show that a teach-in run is required.
  4. Perform Teach-in Run

    Press for 3 seconds.

    The door moves in closing direction to determine the closed position.
    The door carries out a teach-in run.
    The door closes.
    The door is pushed into closed position.
    An existing interlock is taught in.
    The door leaf weight is calculated.
    The door moves at crawl speed in opening direction.
    The opening width and the door leaf weight are saved.
    The operator moves into closed position.
    The teach-in run is finished, the control unit switches to Service Mode 1.
  5. Complete Commissioning

    Press for 3 seconds to exit Service Mode 1.

    Commissioning is complete, the operator is ready for operation.

  6. Final Adjustments